Thank you for taking an interest in the Circuit Breaker NSN parts that we carry here on Buy Military Ground Vehicle Parts. You have reached the RFQ page for part number NEF425030-50DEGC, an item that traces back to the manufacturer Challenger Electrical Equipment Corp. Listed with NSN 5925000626922, this listing is available for purchase from our website at any time. If you are interested in part number NEF425030-50DEGC and wish to learn more, be sure to fill out and submit the RFQ form found on this page. By presenting us information such as your target price and expected delivery date, we can best formulate and present a solution that closely caters to your unique needs and restrictions alike.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-062-6922 Item Description: Circuit Breaker | 5925 | 000626922 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Nef425030-50degc | 2 | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 5.125 INCHES NOMINAL |
CPLM | Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES DC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | FUNGUS RESISTANT |
AKPX | Pole Quantity | 2 |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 480.0 AC AND |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 15000.0 AC AND |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 DC ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.378 INCHES NOMINAL |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CRCF | Trip Release Ambient Temp Rating | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
AJEC | Boss Height | 0.188 INCHES NOMINAL |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRX | Actuator Position Designation | BETWEEN POLE ONE AND TWO |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
ADAT | Body Width | 2.750 INCHES NOMINAL |
CPRW | Actuator Function | TRIP-RESET |
ADTV | Case Material | PLASTIC |
MRC | Decoded Requirement | Clear Text Reply |
ADAQ | Body Length | 6.062 INCHES NOMINAL |
TTQY | Terminal Type And Quantity | 4 COMPRESSION |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 5.219 INCHES NOMINAL |
ADAU | Body Height | 3.406 INCHES NOMINAL |
CPLM | Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES AC AND |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.375 INCHES NOMINAL |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 10000.0 DC ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.225 INCHES NOMINAL |
CPRQ | Reset Method | MANUAL |