Thank you for taking an interest in the Circuitbreaker NSN parts that we carry here on Buy Military Ground Vehicle Parts. You have reached the RFQ page for part number 1SB1065, an item that traces back to the manufacturer Striegel Supply Inc. Listed with NSN 5925008284018, this listing is available for purchase from our website at any time. If you are interested in part number 1SB1065 and wish to learn more, be sure to fill out and submit the RFQ form found on this page. By presenting us information such as your target price and expected delivery date, we can best formulate and present a solution that closely caters to your unique needs and restrictions alike.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-828-4018 Item PartTypeName: CIRCUIT BREAKER | 5925 | 008284018 | P | |||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | ||||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Q0330 | 1 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
ADAT | BODY WIDTH | 2.234 INCHES NOMINAL |
ADAU | BODY HEIGHT | 2.310 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 12.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | WATERTIGHT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 49.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 3 CLIP AND 3 SCREW |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.000 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.156 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 3 TERMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CWJK | CASE MATERIAL | PLASTIC |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.